Dual-Unit Technical Specifications (OD-32U-AC2000)
| Parameter | Engineering Specification | Reference / Notes |
|---|---|---|
| External Dimensions (H × W × D) | 1850 × 800 × 900 mm (72.8 × 31.5 × 35.4 in) | 1000 mm (39.4 in) deep server-chassis option available |
| Usable 19" Rack Envelope | 32U · 720 mm (28.3 in) usable rail depth (820 mm in 1000D) | Heavy-duty 2.0 mm 4-post EIA-310-E rails; 600 kg (1,322 lb) static load |
| Closed-Loop Cooling Capacity | 2,000 W (6,824 BTU/hr) @ L35/L35 | High-ambient +55 °C rotary compressor AC with Modbus RS485 telemetry |
| AC / DC Input Voltage | 220–240V / 50–60Hz standard; 110–120V / 60Hz or 48V DC option | Dedicated 15A/20A AC circuit breaker and phase protection |
| Double-Wall Solar Shield | 25 mm (1.0 in) ventilated 4-side + roof air gap & 20 mm PEF liner | RAL 7035 UV-stabilized marine-grade outdoor polyester finish |
| Enclosure Shell Material | 2.0 mm galvanized steel frame + 1.5 mm double-wall skin (5052 Al / 316L option) | Continuous seam welding with IP55–IP65 compression gaskets |
| Battery Compartment | Optional segregated 8U lower battery zone (300 kg / 660 lb load) | Compatible with 48V rackmount LiFePO4 modules or VRLA strings |
| Ambient Operating Range | -40 °C to +55 °C (-40 °F to +131 °F) with optional 1000W heater | Active dehumidification cycle prevents morning dew point condensation |
| Standards Alignment | NEMA 250 / IEC 60529 IP55–IP65 & EIA-310-E | Built to standard; thermal test sheets available per project |
Target Applications & Operating Fit
- Highway ITS regional hubs combining GPU edge-vision servers, high-port PoE++ switches, and dense fiber distribution
- Utility-scale solar and BESS substations housing SCADA servers, EMS gateways, and grid-tie protection relays
- Open-pit mining private 5G/LTE RAN base stations exposed to conductive iron/copper dust and +50 °C desert heat
- Oilfield wellhead automation and compression stations requiring sealed closed-loop climate control
Structural & Standards Engineering
- High-ambient 2000W (6,824 BTU/hr) closed-loop AC maintains continuous full-load cooling up to +55 °C outdoor ambient with RS485/dry-contact fault reporting.
- Four-sided plus pitched-roof double-wall solar shield creates a passive thermosiphon curtain that blocks direct solar soak.
- 800 mm cabinet width provides dedicated left/right vertical cable management channels for armored fiber trunks and heavy DC busbars.
- Reinforced lifting eyebolts and forklift-channel plinth enable crane or telehandler placement directly onto remote concrete pads.
5-Parameter Engineering Modification Scope
- 1000 mm (39.4 in) extended depth for standard 2U/4U enterprise edge compute servers and GPU appliances
- Redundant dual-AC lead/lag configuration (2 × 1000W or 2 × 2000W) for zero-downtime mission-critical sites
- 316L stainless-steel exterior panels and epoxy-coated condenser coil for coastal or petrochemical atmospheres
- Integrated 1000W thermostatic heater + remote SNMP/Modbus environmental monitoring (temp, humidity, flood, door)
- Custom pre-punched bottom conduit plates, side bulkhead RF/fiber connectors, and recessed utility meter windows
Technical FAQs
How does the OD-32U-AC2000 compare to buying a separate NEMA cabinet and bolting on an Ice Qube or Thermal Edge AC?
You receive a factory-integrated double-wall solar-shielded 19-inch cabinet with pre-engineered cold-aisle baffling, factory-gasketed AC mounting, and verified plinth/rail clearances—eliminating multi-vendor cutout mismatches and separate solar-shield add-on costs.
Should I power the 2000W AC with 110V or 220V?
220–240V (50/60Hz) is preferred at 2000W because operating current is roughly half that of 110V, allowing smaller breaker sizing and lower voltage drop on long outdoor feeder runs. A 110–120V/60Hz variant is available where only single-phase 120V service exists.
Can the OD-32U-AC2000 accommodate standard 750 mm deep 1U/2U rack servers?
Yes—select the 1000 mm (39.4 in) depth option to provide 820 mm (32.3 in) of usable mounting depth plus rear cable bend clearance and front cold-air plenum space.
How is the condenser coil protected in dusty mining or desert sites?
The external condenser loop uses wide-fin hydrophilic aluminum coils with a tool-free washable stainless pre-filter mesh, keeping all dust strictly outside the hermetically sealed IT compartment.
Related Outdoor Network Enclosures Models
12U Pole/Pad Mount + 300W Micro-AC
Compact 12U double-wall solar-shielded cabinet pairing a 300W (1,024 BTU/hr) closed-loop compressor AC with heavy-duty pole/wall/pad brackets for WISP relays and campus fiber nodes.
View Datasheet →24U Double-Wall + 600W AC
Balanced 24U pad-mount double-wall cabinet combining a 600W (2,047 BTU/hr) closed-loop air conditioner with a segregated lower 48V battery bay for WISP distribution hubs and roadside ITS.
View Datasheet →42U Edge-Compute + 4000W AC
Full-height 42U double-wall outdoor micro-data-center enclosure equipped with 4000W (13,648 BTU/hr) closed-loop cooling and 1000–1200 mm server depth for outdoor AI/edge servers, private 5G cores, and utility BESS.
View Datasheet →